Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2016, 09:34 AM
  • 02 1483_02 1482 _20160803_034554.mp4

Date
08/03/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03928
Time
2:34 AM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3671
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1483
Downstream MH
02 1482
Dir. of Survey
Downstream
Length Surveyed
267.1 ft.
Total Length
267.1 ft.
Structural Index
2
Structural Quick
3221
Structural Rating
9
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 02 1483 to 02 1482
MH: 02 1483MH: 02 1482downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 148310.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES40.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"56.8 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES61.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"62.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - WANDERING107.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"131.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"159.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"161.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"192.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"197.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"243.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish243.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"263.1 ft. CC - Crack Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES267.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1482

Observation photos (3)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    10.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    161.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    197.8 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

Observations (19)

DistanceCodeObservation
61.4TF
131.5TFC
243.8CM
0MWL
161.7TF
62.3CMWANDERING
56.8CM
10.8CL
159.2TFC
0MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
40.3TF
192.1TF
107.5TFC
197.8TFA
267.1AMH02 1482
0MWM
0AMH02 1483
263.1CC
243.8TFC

Properties (5)

additional_info
SC306001
custom_field_two
3
customer
LACSD
datetime
2016-08-03T02:34:00-07:00
sewer_category
Gravity