Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2016, 11:17 AM
  • 02 1485_02 1484 _20160801_052908.mp4

Date
08/01/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03930
Time
4:17 AM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3669
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1485
Downstream MH
02 1484
Dir. of Survey
Downstream
Length Surveyed
276.1 ft.
Total Length
276.1 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 02 1485 to 02 1484
MH: 02 1485MH: 02 1484downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14857.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"32.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"54 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"81.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"82.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES109.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"132.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"135.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"139.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES160 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"164.1 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES184.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"211.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"236.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"260.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"276.1 ft. AMH - Downstream Manhole, Survey Ends - 02 1484

Observation photos (5)

  • Water Mark, 10 %of cross sectional area

    0 ft. - Water Mark, 10 %of cross sectional area

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    7.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    82.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    139.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    164.1 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
81.7TFC
0MWM
0MWL
164.1CM
7.2TFC
132.4TFA
54TFC
211.6TFC
260.6TFC
32.7TFA
184.5TF
0AMH02 1485
236.2TFC
160TF
276.1AMH02 1484
82.4CL
139.4CM
135.7TFA
109.1TFC

Properties (5)

additional_info
SC305549
custom_field_two
4
customer
LACSD
datetime
2016-08-01T04:17:00-07:00
sewer_category
Gravity