Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 3, 2016, 06:54 AM
  • 02 1465_02 1464 _20160803_011350.mp4

Date
08/02/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03909
Time
11:54 PM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3671
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
17
Purpose
Routine Assessment
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1464
Downstream MH
02 1465
Dir. of Survey
Upstream
Length Surveyed
329.5 ft.
Total Length
329.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 02 1464 to 02 1465
MH: 02 1464MH: 02 1465upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 14650 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE4.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"7.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"29.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"33.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"53.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"57.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"57.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES80.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"84.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - W/ DEBRIS105.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"109.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"130.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"133.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"155.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"157.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"182.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"185.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"207 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"208.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"231.2 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4"235.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"291 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"293.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"322.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start329.5 ft. AMH - Downstream Manhole, Survey Begins - 02 1464329.5 ft. MWM - Water Mark, 10 %of cross sectional area329.5 ft. VC - Vermin Cockroach329.5 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (4)

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    36.4 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

    143.9 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"

    299.7 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4"

  • General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE

    329.5 ft. - General Observation - CONNECTION AT THE MH 3 O'CLOCK ACTIVE

Observations (31)

DistanceCodeObservation
98.3TFC
325.4TFC
122.5TFC
195.6TFC
329.5AMH02 1465
174TFC
0AMH02 1464
7.2DAGS
0MWM
171.6TFC
244.6TFW/ DEBRIS
223.6TFC
276.1TFA
0VC
329.5DAGS
329.5MGOCONNECTION AT THE MH 3 O'CLOCK ACTIVE
147TFC
296.3TFC
272.4TFC
321.7TFC
0MWL
36.4TFC
272.4CL
121TFC
299.7TF
248.7TFC
38.5TFC
199.2TFA
220.1TFC
94.1TFC
143.9TFA

Properties (5)

additional_info
SC306001
custom_field_two
4
customer
LACSD
datetime
2016-08-02T23:54:00-07:00
sewer_category
Gravity