Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 1, 2016, 10:25 AM
  • 02 1486_02 1485 _20160801_043333.mp4

Date
08/01/2016
W/O
585991
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00309
PipeID
P03931
Time
3:25 AM
Certificate
507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3669
Sewer Name
02 UNION PACIFIC TRUNK
City
COMMERCE, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
16
Purpose
Routine Assessment
Project
WO_585991_TV02189_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 1485
Downstream MH
02 1486
Dir. of Survey
Upstream
Length Surveyed
275.7 ft.
Total Length
275.7 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 02 1485 to 02 1486
MH: 02 1485MH: 02 1486upstream0 ft. AMH - Upstream Manhole, Survey Ends - 02 14860 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK ACTIVE3.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish32.2 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES80.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"104.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"129.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"156.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"180.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"204.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"227.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"249.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"256.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"268.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start275.7 ft. AMH - Downstream Manhole, Survey Begins - 02 1485275.7 ft. MWM - Water Mark, 10 %of cross sectional area275.7 ft. MWL - Water Level, 5 %of cross sectional area

Observation photos (5)

  • Water Level, 5 %of cross sectional area

    0 ft. - Water Level, 5 %of cross sectional area

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    26 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    243.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Finish

    272 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish

Observations (17)

DistanceCodeObservation
47.8TF
18.8TFC
275.7AMH02 1486
146.5TFC
26TF
0AMH02 1485
95.3TFC
7.2DAGS
243.5CL
171TFA
272DAGS
119.6TFC
275.7MGOCONNECTION AT THE MH 9 O'CLOCK ACTIVE
0MWM
0MWL
71TFC
195.3TFC

Properties (5)

additional_info
SC305549
custom_field_two
4
customer
LACSD
datetime
2016-08-01T03:25:00-07:00
sewer_category
Gravity