Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2016, 07:20 AM
  • 02 1596_02 1595_20160816_015053.mpg

Date
08/16/2016
W/O
585987
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00231
PipeID
P04051
Time
12:20 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3420
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 2
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_585987_TV02010_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1596
Downstream MH
02 1595
Dir. of Survey
Downstream
Length Surveyed
217.3 ft.
Total Length
217.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2212
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 02 1596 to 02 1595
MH: 02 1596MH: 02 1595downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 02 15960 ft. VC - Vermin Cockroach0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start39.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"75.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"77.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"83.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"86.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"105.8 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES108.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES121.5 ft. RPP - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES, Start - RPR131.3 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"131.3 ft. RPP - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish - RPR142.9 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"172.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"175.2 ft. TFB - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"189.9 ft. TFB - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"210.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"214.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish217.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1595217.3 ft. VC - Vermin Cockroach217.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 O'CLOCK

Observation photos (15)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    39.4 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    75.4 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    77.9 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    83.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    86.2 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES

    105.8 ft. - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    108.8 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES, Start - RPR

    121.5 ft. - Repair Patch, from 12 to 12 o'clock, within 8 inches of joint: YES, Start - RPR

  • Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    131.3 ft. - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    142.9 ft. - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"

    172.8 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"

  • Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    175.2 ft. - Tap Factory Made Abandoned, at 02 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    189.9 ft. - Tap Factory Made Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    210.4 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (26)

DistanceCodeObservation
0MGOCONNECTION AT THE MH 3 O'CLOCK
217.3AMH02 1595
131.3TFB
0MWL
0MGOCONNECTION AT THE MH 9 O'CLOCK
86.2TFC
175.2TFB
77.9TFC
210.4TFA
105.8FC
75.4TFA
217.3VC
172.8TFC
217.3MGOCONNECTION AT THE MH 9 O'CLOCK
39.4TF
214.4DAGS
121.5RPPRPR
142.9TFB
131.3RPPRPR
108.8CM
189.9TFB
0AMH02 1596
0VC
2DAGS
0MWM
83.3TFC

Properties (5)

additional_info
SC305973
custom_field_two
4
customer
LACSD
datetime
2016-08-16T00:20:21-07:00
sewer_category
Gravity