Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 16, 2016, 08:09 AM
  • 02 1594_02 1593_20160816_025258.mpg

Date
08/16/2016
W/O
585987
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00231
PipeID
P04049
Time
1:09 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3420
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 2
City
LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Routine Assessment
Project
WO_585987_TV02010_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
02 1594
Downstream MH
02 1593
Dir. of Survey
Downstream
Length Surveyed
168.5 ft.
Total Length
168.5 ft.
Structural Index
4
Structural Quick
4131
Structural Rating
7
O&M Index
2
O&M Quick
2F11
O&M Rating
67
Overall Index
2
Overall Quick
Overall Rating
74
Pipe schematic from manhole 02 1594 to 02 1593
MH: 02 1594MH: 02 1593downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 15942 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES67.4 ft. TBB - Tap Break-In Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"112.1 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES143.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"165.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish168.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1593168.5 ft. VC - Vermin Cockroach

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    6 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Tap Break-In Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"

    67.4 ft. - Tap Break-In Abandoned, at 10 o'clock, -, within 8 inches of joint: NO, 4"

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

    112.1 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

    143.6 ft. - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"

Observations (11)

DistanceCodeObservation
112.1FM
143.6TFC
67.4TBB
0MWM
0MWL
168.5AMH02 1593
0AMH02 1594
2DAGS
168.5VC
6FL
165.3DAGS

Properties (5)

additional_info
SC305973
custom_field_two
3
customer
LACSD
datetime
2016-08-16T01:09:33-07:00
sewer_category
Gravity