Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 29, 2015, 05:46 AM
  • 21 1061_21 1060A_20151228_215934.mp4

Date
12/28/2015
W/O
547133
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00769
PipeID
P26487
Time
9:46 PM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3019
Sewer Name
21 GAREY AVENUE TRUNK
City
POMONA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
06
Purpose
Routine Assessment
Project
WO_547133_TV21036_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
21 1061
Downstream MH
21 1060A
Dir. of Survey
Downstream
Length Surveyed
202 ft.
Total Length
202 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
2112
O&M Rating
4
Overall Index
1
Overall Quick
Overall Rating
4
Pipe schematic from manhole 21 1061 to 21 1060A
MH: 21 1061MH: 21 1060Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 21 10610 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 15 %of cross sectional area2.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start27 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YES41.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"88.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"141.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"189.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"198.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish202 ft. AMH - Downstream Manhole, Survey Ends - 21 1060A202 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK ACTIVE

Observations (13)

DistanceCodeObservation
88.6TFC
27RFJ
141.9TFC
202AMH21 1060A
0AMH21 1061
202MGOLATERAL AT MH 9 O'CLOCK ACTIVE
189.8TFC
0MWM
2.2DAGS
41.1TFC
0VC
0MWL
198.7DAGS

Properties (5)

additional_info
SC224611
custom_field_two
4
customer
LACSD
datetime
2015-12-28T21:46:46-08:00
sewer_category
GRAVITY