Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 3, 2016, 07:35 AM
  • 32 1086_32 1085_02022016_233546.mp4

Date
02/02/2016
W/O
547105
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19535
Time
11:35 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3091
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_547105_TV32026_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1086
Downstream MH
32 1085
Dir. of Survey
Downstream
Length Surveyed
227.8 ft.
Total Length
227.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2H00
O&M Rating
92
Overall Index
2
Overall Quick
Overall Rating
92
Pipe schematic from manhole 32 1086 to 32 1085
MH: 32 1086MH: 32 1085downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10860 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS39.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"46.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"100.6 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"113 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"173.4 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"179.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"222 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"226.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish227.8 ft. AMH - Downstream Manhole, Survey Ends - 32 1085

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

    15.7 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ROOTS

Observations (15)

DistanceCodeObservation
226.2DAGS
2DAGS
0MWM
0MWL
173.4TFA
15.7TFDROOTS
0AMH32 1086
227.8AMH32 1085
113TFA
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
46.1TFA
39.8TFC
179.2TFA
100.6TFA
222TFA

Properties (5)

additional_info
SC225469
custom_field_two
4
customer
LACSD
datetime
2016-02-02T23:35:30-08:00
sewer_category
GRAVITY