Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2016, 08:02 AM
  • 32 1106_32 1105_29012016_000242.mp4

Date
01/29/2016
W/O
547105
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19556
Time
12:02 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3088
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_547105_TV32026_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
32 1106
Downstream MH
32 1105
Dir. of Survey
Downstream
Length Surveyed
124.8 ft.
Total Length
124.8 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
412D
O&M Rating
52
Overall Index
2
Overall Quick
Overall Rating
57
Pipe schematic from manhole 32 1106 to 32 1105
MH: 32 1106MH: 32 1105downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 11060 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start43.8 ft. CS - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES45.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES123.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish124.8 ft. AMH - Downstream Manhole, Survey Ends - 32 1105

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

    43.8 ft. - Crack Spiral, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    45.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0MWM
0AMH32 1106
45.4CM
2DAGS
0MWL
123.5DAGS
124.8AMH32 1105
43.8CS

Properties (5)

additional_info
SC225466
custom_field_two
3
customer
LACSD
datetime
2016-01-29T00:02:17-08:00
sewer_category