Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2016, 11:22 AM
  • 32 1069_32 1068_29012016_032303.mp4

Date
01/29/2016
W/O
547105
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19517
Time
3:22 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3088
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_547105_TV32026_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
32 1069
Downstream MH
32 1068
Dir. of Survey
Downstream
Length Surveyed
372.8 ft.
Total Length
372.8 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
2
O&M Quick
312N
O&M Rating
151
Overall Index
2
Overall Quick
Overall Rating
162
Pipe schematic from manhole 32 1069 to 32 1068
MH: 32 1069MH: 32 1068downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10690 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start21 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"27.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.6 ft. MGO - General Observation - ABANDONED MH44.5 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES44.5 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"44.5 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"101.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"106.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"178.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.1 ft. FS - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES193 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start197.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish211 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES231.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"236.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"326.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"331.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"371 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish372.8 ft. AMH - Downstream Manhole, Survey Ends - 32 1068

Observation photos (7)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    36.6 ft. - General Observation - ABANDONED MH

  • Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

    44.5 ft. - Roots Medium Lateral, from 01 to 05 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    44.5 ft. - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

    186.1 ft. - Fracture Spiral, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    193 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    211 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
372.8AMH32 1068
2DAGS
183.6TFC
36.6MGOABANDONED MH
0MWM
44.5RML
21TFC
331.8TFA
44.5TBA
106.3TFC
236.2TFA
44.5TBA
101.3TFC
371DAGS
0MWL
193FL
0AMH32 1069
27.9TFC
0MWL
326.4TFC
231.1TFA
186.1FS
197.7FL
178.4TFC
211CL

Properties (5)

additional_info
SC225466
custom_field_two
3
customer
LACSD
datetime
2016-01-29T03:22:28-08:00
sewer_category
GRAVITY