Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 2, 2016, 07:45 AM
  • 32 1095_32 1094_01022016_234529.mp4

Date
02/01/2016
W/O
547105
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19544
Time
11:45 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3090
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_547105_TV32026_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1095
Downstream MH
32 1094
Dir. of Survey
Downstream
Length Surveyed
174.2 ft.
Total Length
174.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2F00
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole 32 1095 to 32 1094
MH: 32 1095MH: 32 1094downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CAPPED CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 32 10950 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start82.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 6"112.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"172 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish174.2 ft. AMH - Downstream Manhole, Survey Ends - 32 1094174.2 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
2DAGS
174.2AMH32 1094
0MWM
143.3TFC
0MGOCAPPED CONNECTION AT MH 9 O'CLOCK
174.2MGOCAPPED CONNECTION AT MH 3 O'CLOCK
172DAGS
82.7TFA
0AMH32 1095
0MWL
112.9TFC

Properties (5)

additional_info
SC225468
custom_field_two
4
customer
LACSD
datetime
2016-02-01T23:45:13-08:00
sewer_category
GRAVITY