Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 29, 2016, 11:53 AM
  • 32 1067_32 1066_29012016_035429.mp4

Date
01/29/2016
W/O
547105
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19515
Time
3:53 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3088
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
06
Purpose
Routine Assessment
Project
WO_547105_TV32026_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
32 1067
Downstream MH
32 1066
Dir. of Survey
Downstream
Length Surveyed
356 ft.
Total Length
356 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
322M
O&M Rating
146
Overall Index
2
Overall Quick
Overall Rating
149
Pipe schematic from manhole 32 1067 to 32 1066
MH: 32 1067MH: 32 1066downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10672 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start35.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"40.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"77.1 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"184.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"262 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES262 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.3 ft. CM - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES336 ft. RMJ - Roots Medium Joint, from 09 to 01 o'clock, 20 %, within 8 inches of joint: YESR339.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"344.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"353.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish356 ft. AMH - Downstream Manhole, Survey Ends - 32 1066

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    77.1 ft. - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

    262 ft. - Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    262 ft. - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

    288.3 ft. - Crack Multiple, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Roots Medium Joint, from 09 to 01 o'clock, 20 %, within 8 inches of joint: YESR

    336 ft. - Roots Medium Joint, from 09 to 01 o'clock, 20 %, within 8 inches of joint: YESR

Observations (21)

DistanceCodeObservation
336RMJ
266.8TFC
117.6TFC
184.4TFA
2DAGS
344.2TFC
40.8TFC
353.3DAGS
262RML
0MWM
262TFA
77.1TBA
356AMH32 1066
189.3TFC
112.3TFA
339.1TFA
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
288.3CM
0MWL
35.7TFA
0AMH32 1067

Properties (5)

additional_info
SC225466
custom_field_two
4
customer
LACSD
datetime
2016-01-29T03:53:56-08:00
sewer_category
GRAVITY