Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2016, 05:45 AM
  • 01 0190_01 0189_30082016_224538.mpg

Date
08/30/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01231
Time
10:45 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3576
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0190
Downstream MH
01 0189
Dir. of Survey
Downstream
Length Surveyed
259.2 ft.
Total Length
259.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0190 to 01 0189
MH: 01 0190MH: 01 0189downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 01900 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area3.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start30 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"88.2 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"166.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"180.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN192.1 ft. DSZ - Deposits Settled Other, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO204.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.1 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish259.2 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK CAPPED259.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0189

Observation photos (3)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    88.2 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

    180.8 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6" - BROKEN

Observations (20)

DistanceCodeObservation
0AMH01 0190
0MGOLATERAL AT MH 9 OCLOCK
130.8TF
204.2TF
259.2MGOLATERAL AT MH 3 OCLOCK CAPPED
0MWL
83.9TF
91.9TFC
192.1DSZ
180.8TFDBROKEN
3.4CM
142.2TFC
227.8TFC
259.2AMH01 0189
0MWM
252.1CM
88.2TB
166.2TFC
30TFC
62.7TFC

Properties (5)

additional_info
SC306166
custom_field_two
3
customer
LACSD
datetime
2016-08-30T22:45:00-07:00
sewer_category