Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2016, 11:03 AM
  • 01 0192_01 0191A_300816_040616.mpg

Date
08/30/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01234
Time
4:03 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3575
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0192
Downstream MH
01 0191A
Dir. of Survey
Downstream
Length Surveyed
23.3 ft.
Total Length
23.3 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 01 0192 to 01 0191A
MH: 01 0192MH: 01 0191Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 019213.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start19.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish23.3 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK23.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0191A

Observation photos (1)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    13.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
19.1CL
13.6CL
0MWM
23.3MGOLATERAL AT MH 9 OCLOCK
0MWL
23.3AMH01 0191A
0AMH01 0192

Properties (5)

additional_info
SC306165
custom_field_two
3
customer
LACSD
datetime
2016-08-30T04:03:30-07:00
sewer_category
Gravity