Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2016, 09:53 AM
  • 01 0178B_01 0178A_31082016_025736.mpg

Date
08/31/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01217
Time
2:53 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3576
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0178A
Downstream MH
01 0178B
Dir. of Survey
Upstream
Length Surveyed
324 ft.
Total Length
324 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 01 0178A to 01 0178B
MH: 01 0178AMH: 01 0178Bupstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 0178B0.1 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK29.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"59.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"111.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"156 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"170.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"179.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.9 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES208.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"228.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"285.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"314.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"324 ft. AMH - Downstream Manhole, Survey Begins - 01 0178A324 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK324 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK324 ft. MWL - Water Level, 5 %of cross sectional area324 ft. MWM - Water Mark, 5 %of cross sectional area

Observation photos (1)

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    116.1 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
212.2TFC
65.2TFC
0AMH01 0178A
0MGOLATERAL AT MH 3 OCLOCK
153.3TF
221.2TF
264.8TFC
168TFC
0MGOLATERAL AT MH 9 OCLOCK
9.4TFC
115.3TF
267.7TFC
238.8TFC
0MWL
95.3TFC
144.9TF
253.1TF
324AMH01 0178B
116.1CM
97.7TF
323.9MGOLATERAL AT MH 9 OCLOCK
191.4TFC
294.1TFC
38.6TF
0MWM
11.9TFC

Properties (5)

additional_info
SC306166
custom_field_two
4
customer
LACSD
datetime
2016-08-31T02:53:47-07:00
sewer_category
Gravity