Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 31, 2016, 06:24 AM
  • 01 0187_01 0186_30082016_232523.mpg

Date
08/30/2016
W/O
585995
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00202
PipeID
P01228
Time
11:24 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3576
Sewer Name
01 COMPTON AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_585995_TV01012_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0187
Downstream MH
01 0186
Dir. of Survey
Downstream
Length Surveyed
189.4 ft.
Total Length
189.4 ft.
Structural Index
4
Structural Quick
4231
Structural Rating
11
O&M Index
1
O&M Quick
2113
O&M Rating
5
Overall Index
2
Overall Quick
Overall Rating
16
Pipe schematic from manhole 01 0187 to 01 0186
MH: 01 0187MH: 01 0186downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 01870 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK0 ft. MWL - Water Level, 20 %of cross sectional area5.4 ft. FM - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES10.7 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start13.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"34.2 ft. RFJ - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES35.4 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start35.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish46.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"48.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"67.5 ft. RFB - Roots Fine Barrell, at 09 o'clock84.2 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES90.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"93 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.5 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start119.3 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish140.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"143.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"171 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish189.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0186189.4 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK CAPPED

Observation photos (7)

  • Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    5.4 ft. - Fracture Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    10.7 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

    34.2 ft. - Roots Fine Joint, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    35.4 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Barrell, at 09 o'clock

    67.5 ft. - Roots Fine Barrell, at 09 o'clock

  • Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES

    84.2 ft. - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    95.5 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
0AMH01 0187
35.4FM
10.7CM
90.6TFC
189.4AMH01 0186
95.5RFJ
35.4CM
34.2RFJ
171FM
0MWM
5.4FM
93TFC
46.1TFC
0MGOLATERAL AT MH 3 OCLOCK
119.3RFJ
143.3TFC
189.4MGOLATERAL AT MH 3 OCLOCK CAPPED
140.7TFC
67.5RFB
0MWL
13.3TFC
84.2RFJ
48.5TFC

Properties (5)

additional_info
SC306166
custom_field_two
2
customer
LACSD
datetime
2016-08-30T23:24:13-07:00
sewer_category
Gravity