Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2016, 09:19 AM
  • 01 0987_01 1097_13092016_021938.mp4

Date
09/13/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01827
Time
2:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3581
Sewer Name
01 VERNON EXTENSION TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0987
Downstream MH
01 1097
Dir. of Survey
Downstream
Length Surveyed
406.5 ft.
Total Length
406.5 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 01 0987 to 01 1097
MH: 01 0987MH: 01 1097downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 09870 ft. MWM - Water Mark, 20 %of cross sectional area24.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"60.9 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES66.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES191.3 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"406.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK406.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK406.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1097

Observation photos (3)

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    60.9 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

    73 ft. - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    191.3 ft. - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (11)

DistanceCodeObservation
0MWL
73CC
66.6TFC
406.5MGOCONNECTION AT MH 3 O'CLOCK
191.3TBC
0AMH01 0987
24.2TFC
406.5MGOCONNECTION AT MH 9 O'CLOCK
0MWM
406.5AMH01 1097
60.9CL

Properties (5)

additional_info
SC306174
custom_field_two
4
customer
LACSD
datetime
2016-09-13T02:19:21-07:00
sewer_category
Gravity