Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 13, 2016, 07:15 AM
  • 01 0992_01 0991_13092016_001551.mp4

Date
09/13/2016
W/O
585982
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00221
PipeID
P01832
Time
12:15 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3581
Sewer Name
01 VERNON EXTENSION TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
WO_585982_TV01065_AUG2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 0992
Downstream MH
01 0991
Dir. of Survey
Downstream
Length Surveyed
302.5 ft.
Total Length
302.5 ft.
Structural Index
2
Structural Quick
2100
Structural Rating
2
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 01 0992 to 01 0991
MH: 01 0992MH: 01 0991downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 09920 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area122.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"193 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES205.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0991

Observation photos (3)

  • Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    122.8 ft. - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    193 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    205.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (7)

DistanceCodeObservation
302.5AMH01 0991
0AMH01 0992
122.8TBC
0MWM
205.6TB
193CL
0MWL

Properties (5)

additional_info
SC306174
custom_field_two
4
customer
LACSD
datetime
2016-09-13T00:15:34-07:00
sewer_category
Gravity