Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jun 28, 2016, 05:20 AM
  • 02 0881_02 0880 _062716_222124.mpg

Date
06/27/2016
W/O
580416
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00249
PipeID
P03448
Time
10:20 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3545
Sewer Name
02 DOWNEY TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
27
Purpose
Routine Assessment
Project
WO_580416_TV02050_JULY2016
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
02 0881
Downstream MH
02 0880
Dir. of Survey
Downstream
Length Surveyed
292.3 ft.
Total Length
292.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 02 0881 to 02 0880
MH: 02 0881MH: 02 0880downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 08810 ft. MWM - Water Mark, 20 %of cross sectional area4.2 ft. MGO - General Observation - MAG COAT 80%46.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES56.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"252.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"292.3 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 9 O'CLOCK292.3 ft. MGO - General Observation - CONNECTION AT THE MH CAPPED 3 O'CLOCK292.3 ft. AMH - Downstream Manhole, Survey Ends - 02 0880

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    53.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (12)

DistanceCodeObservation
292.3MGOCONNECTION AT THE MH CAPPED 9 O'CLOCK
0MWL
153.2TFA
0AMH02 0881
292.3MGOCONNECTION AT THE MH CAPPED 3 O'CLOCK
56.5TF
252.8TFA
46.6TF
53.5DAGS
0MWM
4.2MGOMAG COAT 80%
292.3AMH02 0880

Properties (5)

additional_info
SC305858
custom_field_two
4
customer
LACSD
datetime
2016-06-27T22:20:36-07:00
sewer_category