Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 30, 2017, 03:19 PM
  • C 0171_C 0170_5302017_083303.mp4

Date
05/30/2017
W/O
0635652
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00130
PipeID
P09695
Time
8:19 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7419
Sewer Name
C JOINT OUTFALL C - UNIT 5C
City
LONG BEACH
Loc. details
Parking Lot
Location Code
G
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20170530DF_JOINT_OUTFALL_C_UNIT_5C
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Upstream MH
C 0171
Downstream MH
C 0170
Dir. of Survey
Downstream
Length Surveyed
197.3 ft.
Total Length
197.3 ft.
Structural Index
4
Structural Quick
5331
Structural Rating
20
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
26
Pipe schematic from manhole C 0171 to C 0170
MH: C 0171MH: C 0170downstream0 ft. AMH - Upstream Manhole, Survey Begins - 8:20 AM0.1 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0.1 ft. MWM - Water Mark, 35 %of cross sectional area0.1 ft. MWL - Water Level, 30 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - ROACHES @ MH2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.4 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - 11 O'CLOCK27.2 ft. MGO - General Observation - SPALLING/AGGREGATE51.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES73.8 ft. SRV - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES103.2 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start113.4 ft. MGP - General Photograph - RIB CAGE REINFORCEMENT140.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES173.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES195.1 ft. SRC - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish195.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish195.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish197.3 ft. MGO - General Observation - ROACHES @ MH197.3 ft. MGO - General Observation - Conn. @ Mh, 5 O' Clock. Active197.3 ft. AMH - Downstream Manhole, Survey Ends - 9:11 AM197.3 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active

Observation photos (10)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - 11 O'CLOCK

    9.4 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - 11 O'CLOCK

  • General Observation - SPALLING/AGGREGATE

    27.2 ft. - General Observation - SPALLING/AGGREGATE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES

    51.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

    73.8 ft. - Surface Reinforcement Visible, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    103.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Photograph - RIB CAGE REINFORCEMENT

    113.4 ft. - General Photograph - RIB CAGE REINFORCEMENT

  • Deposits Attached Grease, 5 %of cross sectional area, from 01 to 05 o'clock,  , within 8 inches of joint: YES

    140.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 01 to 05 o'clock, , within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    173.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
140.5DAGS
195.1SRC
197.3MGOROACHES @ MH
9.4SRV11 O'CLOCK
197.3MGOConn. @ Mh, 5 O' Clock. Active
173.6DAGS
0.1MGOConn. @ Mh, 3 O' Clock. Active
195.1SSS
73.8SRV
51.7DAGS
27.2MGOSPALLING/AGGREGATE
197.3AMH9:11 AM
2SSS
103.2SRC
0.1MWM
0.1MWL
195.1SAV
197.3MGOConn. @ Mh, 3 O' Clock. Active
0AMH8:20 AM
2MGOROACHES @ MH
113.4MGPRIB CAGE REINFORCEMENT
2SAV

Properties (4)

additional_info
FOOTAGE MEASURED ONLY 198' FROM MH C 0171 TO MH C 0170. (THE PAPERWORK SAYS IT IS 329.43')
custom_field_two
2
customer
LACSD
datetime
2017-05-30T08:19:08-07:00