Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 26, 2017, 09:22 AM
  • 01 1229_01 1228_5262017_023007.mp4

Date
05/26/2017
W/O
0635395
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00217
PipeID
P02053
Time
2:22 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0538
Sewer Name
01 SANTA FE AVENUE TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
20170526MDM_SANTA_FE_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
01 1229
Downstream MH
01 1228
Dir. of Survey
Downstream
Length Surveyed
162.8 ft.
Total Length
162.8 ft.
Structural Index
2
Structural Quick
312D
Structural Rating
55
O&M Index
2
O&M Quick
2300
O&M Rating
6
Overall Index
2
Overall Quick
Overall Rating
61
Pipe schematic from manhole 01 1229 to 01 1228
MH: 01 1229MH: 01 1228downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:25AM3.7 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - HAIRLINE8.5 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - H11.1 ft. FC - Fracture Circumferential, from 02 to 03 o'clock, within 8 inches of joint: YES - H13.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES16.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - H19 ft. FC - Fracture Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES - H22.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped24 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - H26.3 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - H28.3 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS28.3 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS28.3 ft. MGO - General Observation - 15" VCP36.4 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL43.9 ft. FC - Fracture Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES - SL54 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - L56.5 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL57.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open59.1 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL72.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped74.2 ft. FC - Fracture Circumferential, from 01 to 03 o'clock, within 8 inches of joint: YES - SL75.1 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open76.8 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL104.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: NO109.8 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL122.5 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL123.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open132.5 ft. FC - Fracture Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES - SL140.4 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL140.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL145.4 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL148.1 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SL148.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open150.4 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL152.8 ft. FC - Fracture Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES - SL152.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 11 to 01 o'clock, , within 8 inches of joint: YES155.3 ft. FC - Fracture Circumferential, from 12 to 02 o'clock, within 8 inches of joint: YES - SL157.9 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - SL162.2 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - 70% AT JOINTS162.2 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish - 25% AT JOINTS162.8 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observations (44)

DistanceCodeObservation
16.1FCH
157.9FCSL
148.1FCSL
122.5FCSL
26.3FCH
57.7TFOpen
104.3DAGS
140.4FCSL
155.3FCSL
162.8AMH3:05AM
0MWM
75.1TBOpen
36.4FCSL
152.8FCSL
140.4FCSL
59.1FCSL
28.3FCHAIRLINE AT JOINTS
152.8DAGS
148.9TFOpen
56.5FCSL
162.2FC70% AT JOINTS
0MGOConn. @ Mh, 9 O' Clock. Active
19FCH
0MWL
72.8TFCCapped
145.4FCSL
3.7FCHAIRLINE
54FCL
13.8DAGS
74.2FCSL
8.5FCH
150.4FCSL
24FCH
123.8TFOpen
132.5FCSL
0AMH2:25AM
109.8FCSL
11.1FCH
28.3FLHAIRLINE AT JOINTS
43.9FCSL
162.2FL25% AT JOINTS
28.3MGO15" VCP
22.3TFCCapped
76.8FCSL

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2017-05-26T02:22:32-07:00