Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2016, 07:10 AM
  • 32 1042_32 1041_20160205_002147.mp4

Date
02/04/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19490
Time
11:10 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3094
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1042
Downstream MH
32 1041
Dir. of Survey
Downstream
Length Surveyed
354 ft.
Total Length
354 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
176
O&M Index
2
O&M Quick
2[00
O&M Rating
280
Overall Index
2
Overall Quick
Overall Rating
456
Pipe schematic from manhole 32 1042 to 32 1041
MH: 32 1042MH: 32 1041downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 10420 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start41.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES47.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES52.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES68.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY348.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish352 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish352 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish354 ft. AMH - Downstream Manhole, Survey Ends - 32 1041

Observation photos (6)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    41.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    47.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    52.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

    68.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

Observations (13)

DistanceCodeObservation
0AMH32 1042
0MWM
68.2CMSPORADICALLY
354AMH32 1041
352DAE
47.7CM
0MWL
52.4CL
2DAE
348.9CM
2DAGS
352DAGS
41.9CM

Properties (5)

additional_info
SC225472
custom_field_two
3
customer
LACSD
datetime
2016-02-04T23:10:34-08:00
sewer_category
GRAVITY