Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2016, 11:32 AM
  • 32 1034_32 1033_20160205_044857.mp4

Date
02/05/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19482
Time
3:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3094
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
32 1034
Downstream MH
32 1033
Dir. of Survey
Downstream
Length Surveyed
351.4 ft.
Total Length
351.4 ft.
Structural Index
3
Structural Quick
3300
Structural Rating
9
O&M Index
2
O&M Quick
2M00
O&M Rating
144
Overall Index
2
Overall Quick
Overall Rating
153
Pipe schematic from manhole 32 1034 to 32 1033
MH: 32 1034MH: 32 1033downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 10340 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start231.7 ft. CM - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES257.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES303.8 ft. CM - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES341 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start350.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish351.3 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK351.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE351.4 ft. AMH - Downstream Manhole, Survey Ends - 32 1033

Observation photos (6)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

    231.7 ft. - Crack Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    257.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

    303.8 ft. - Crack Multiple, from 10 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    341 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    351.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
351.4AMH32 1033
351.3MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH32 1034
231.7CM
303.8CM
351.3MGOCOCKROACHES IN MANHOLE
350.1DAGS
0MWL
257.9CM
2DAGS
350.1DAE
341DAE
0MWM

Properties (5)

additional_info
SC225472
custom_field_two
4
customer
LACSD
datetime
2016-02-05T03:32:04-08:00
sewer_category
GRAVITY