Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 5, 2016, 07:38 AM
  • 32 1040A_32 1040_20160205_004606.mp4

Date
02/04/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19489
Time
11:38 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3094
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1040A
Downstream MH
32 1040
Dir. of Survey
Downstream
Length Surveyed
127.9 ft.
Total Length
127.9 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
2
O&M Quick
2D00
O&M Rating
50
Overall Index
2
Overall Quick
Overall Rating
56
Pipe schematic from manhole 32 1040A to 32 1040
MH: 32 1040AMH: 32 1040downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 1040A0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start42.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES79.5 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES126.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish127.9 ft. AMH - Downstream Manhole, Survey Ends - 32 1040

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    42.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    79.5 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

Observations (9)

DistanceCodeObservation
79.5CM
0AMH32 1040A
0MWM
126.4DAGS
42.6CM
0MWL
2DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
127.9AMH32 1040

Properties (5)

additional_info
SC225472
custom_field_two
3
customer
LACSD
datetime
2016-02-04T23:38:36-08:00
sewer_category
GRAVITY