Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2016, 11:52 AM
  • 32 1024_32 1023_20160208_050639.mp4

Date
02/08/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19472
Time
3:52 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3095
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1024
Downstream MH
32 1023
Dir. of Survey
Downstream
Length Surveyed
350 ft.
Total Length
350 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
188
O&M Index
2
O&M Quick
2Z00
O&M Rating
274
Overall Index
2
Overall Quick
Overall Rating
462
Pipe schematic from manhole 32 1024 to 32 1023
MH: 32 1024MH: 32 1023downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 10240 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.3 ft. CL - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES7.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start27.5 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES43 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY345.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish348.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK350 ft. AMH - Downstream Manhole, Survey Ends - 32 1023

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    7.3 ft. - Crack Longitudinal, at 01 o'clock, within 8 inches of joint: YES

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    7.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    27.5 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

    43 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

Observations (13)

DistanceCodeObservation
350MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH32 1024
43CMSPORADICALLY
348.2DAE
2DAGS
0MWL
348.2DAGS
27.5CM
345.6CM
350AMH32 1023
7.3CL
7.4DAE
0MWM

Properties (5)

additional_info
SC225473
custom_field_two
3
customer
LACSD
datetime
2016-02-08T03:52:26-08:00
sewer_category
GRAVITY