32 1029_32 1028_20160208_031517.mp4
2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start
2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start
6.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES
11.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES
16.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY
310.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES
320 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES
| Distance | Code | Observation |
|---|---|---|
| 0 | MWL | — |
| 320 | FM | — |
| 16.8 | CM | SPORADICALLY |
| 88.3 | DAE | — |
| 11.4 | CM | — |
| 0 | AMH | 32 1029 |
| 6.3 | CL | — |
| 2 | DAGS | — |
| 0 | MWM | — |
| 371.9 | DAGS | — |
| 310.5 | FM | — |
| 371 | CM | — |
| 2 | DAE | — |
| 373.8 | AMH | 32 1028 |