Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 10, 2016, 08:10 AM
  • 32 1009_32 1008_20160210_012411.mp4

Date
02/10/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19457
Time
12:10 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3097
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1009
Downstream MH
32 1008
Dir. of Survey
Downstream
Length Surveyed
341 ft.
Total Length
341 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
159
O&M Index
2
O&M Quick
2Z00
O&M Rating
268
Overall Index
2
Overall Quick
Overall Rating
427
Pipe schematic from manhole 32 1009 to 32 1008
MH: 32 1009MH: 32 1008downstream0 ft. AMH - Upstream Manhole, Survey Begins - 32 10090 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start72.7 ft. CM - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES77.8 ft. CM - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES82.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY168.8 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"337.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish338.6 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish338.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish341 ft. AMH - Downstream Manhole, Survey Ends - 32 1008

Observation photos (5)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

    72.7 ft. - Crack Multiple, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

    77.8 ft. - Crack Multiple, from 10 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

    82.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

Observations (14)

DistanceCodeObservation
168.8TBA
0AMH32 1009
77.8CM
0MWL
338.6DAE
337.1CM
0MWM
2DAE
2DAGS
250.9TBA
72.7CM
82.5CMSPORADICALLY
341AMH32 1008
338.6DAGS

Properties (5)

additional_info
SC225475
custom_field_two
3
customer
LACSD
datetime
2016-02-10T00:10:13-08:00
sewer_category
GRAVITY