Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 9, 2016, 11:58 AM
  • 32 1012_32 1011_20160209_051215.mp4

Date
02/09/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19460
Time
3:58 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3096
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1012
Downstream MH
32 1011
Dir. of Survey
Downstream
Length Surveyed
355 ft.
Total Length
355 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
201
O&M Index
2
O&M Quick
2[11
O&M Rating
281
Overall Index
2
Overall Quick
Overall Rating
482
Pipe schematic from manhole 32 1012 to 32 1011
MH: 32 1012MH: 32 1011downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10122 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start9.8 ft. CM - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES21 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start106.9 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR353.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.3 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish353.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish355 ft. AMH - Downstream Manhole, Survey Ends - 32 1011355 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

    9.8 ft. - Crack Multiple, from 08 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

    106.9 ft. - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YESR

Observations (13)

DistanceCodeObservation
2DAGS
355AMH32 1011
355MGOACTIVE CONNECTION AT MH 9 O'CLOCK
353.3CM
2DAE
0MWM
353.3DAE
0MWL
9.8CM
353.3DAGS
0AMH32 1012
21CM
106.9RFJ

Properties (5)

additional_info
SC225474
custom_field_two
4
customer
LACSD
datetime
2016-02-09T03:58:05-08:00
sewer_category
GRAVITY