Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 9, 2016, 10:15 AM
  • 32 1015_32 1014_20160209_032929.mp4

Date
02/09/2016
W/O
547104
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19463
Time
2:15 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3096
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
05
Purpose
Routine Assessment
Project
WO_547104_TV32025_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
32 1015
Downstream MH
32 1014
Dir. of Survey
Downstream
Length Surveyed
350.7 ft.
Total Length
350.7 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
174
O&M Index
2
O&M Quick
2[00
O&M Rating
276
Overall Index
2
Overall Quick
Overall Rating
450
Pipe schematic from manhole 32 1015 to 32 1014
MH: 32 1015MH: 32 1014downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10150 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start6.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES21.6 ft. CM - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES47.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES72.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY259.8 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"259.8 ft. CC - Crack Circumferential, from 10 to 04 o'clock, within 8 inches of joint: NO349 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish349 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish349 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350.7 ft. AMH - Downstream Manhole, Survey Ends - 32 1014

Observation photos (7)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    6.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

    21.6 ft. - Crack Multiple, from 09 to 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    47.2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

    72.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SPORADICALLY

  • Crack Circumferential, from 10 to 04 o'clock, within 8 inches of joint: NO

    259.8 ft. - Crack Circumferential, from 10 to 04 o'clock, within 8 inches of joint: NO

Observations (15)

DistanceCodeObservation
0MWL
6.6CL
21.6CM
47.2CM
72.9CMSPORADICALLY
2DAE
0AMH32 1015
349CM
259.8TBA
349DAE
2DAGS
259.8CC
0MWM
349DAGS
350.7AMH32 1014

Properties (5)

additional_info
SC225474
custom_field_two
3
customer
LACSD
datetime
2016-02-09T02:15:25-08:00
sewer_category
SIPHON