Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 27, 2016, 12:46 PM
  • G 0142_G 0141_20160127_055233_.mp4

Date
01/27/2016
W/O
547569
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01180
PipeID
P01465
Time
4:46 AM
Certificate
U-507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3128
Sewer Name
G JOINT OUTFALL G - UNIT 8
City
COMPTON, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_547569_TV01236_JAN2016
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
G 0142
Downstream MH
G 0141
Dir. of Survey
Downstream
Length Surveyed
17.3 ft.
Total Length
17.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
5
Pipe schematic from manhole G 0142 to G 0141
MH: G 0142MH: G 0141downstream0 ft. AMH - Upstream Manhole, Survey Begins - G 01420 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWL - Water Level, 65 %of cross sectional area0 ft. MWM - Water Mark, 85 %of cross sectional area2 ft. MGO - General Observation - MAGNESIUM H.O. START17.2 ft. MGO - General Observation - MISSING TILES17.3 ft. MSA - Survey Abandoned - DUE TO SLOW FLOW AND HIGH WATER LEVEL CAUSING BOAT TO HIT TOP OF PIPE17.3 ft. MGO - General Observation - FLOW TO SLOW TO PULL CAMERA THROUGH PIPE

Observation photos (1)

  • Water Mark, 85 %of cross sectional area

    0 ft. - Water Mark, 85 %of cross sectional area

Observations (8)

DistanceCodeObservation
0AMHG 0142
17.2MGOMISSING TILES
2MGOMAGNESIUM H.O. START
17.3MSADUE TO SLOW FLOW AND HIGH WATER LEVEL CAUSING BOAT TO HIT TOP OF PIPE
0MGOLATERAL AT MH 9 OCLOCK
0MWL
17.3MGOFLOW TO SLOW TO PULL CAMERA THROUGH PIPE
0MWM

Properties (5)

additional_info
SC225515
custom_field_two
5
customer
LACSD
datetime
2016-01-27T04:46:33-08:00
sewer_category
GRAVITY