Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2016, 08:57 AM
  • 02 1547_02 1546A_20160113_011610_.mp4

Date
01/13/2016
W/O
544149
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00230
PipeID
P03979
Time
12:57 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2954
Sewer Name
02 ARIZONA AVENUE TRUNK, SECTION 1
City
LOS ANGELES
Loc. details
Alley
Location Code
H
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_544149_TV02006_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
02 1547
Downstream MH
02 1546A
Dir. of Survey
Downstream
Length Surveyed
198.9 ft.
Total Length
198.9 ft.
Structural Index
3
Structural Quick
3G00
Structural Rating
117
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
119
Pipe schematic from manhole 02 1547 to 02 1546A
MH: 02 1547MH: 02 1546Adownstream0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 15470 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK0 ft. MWM - Water Mark, 45 %of cross sectional area5.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"50.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"70.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"73 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"95.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"98.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"123.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 4"146.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"148.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"174.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"198.9 ft. AMH - Downstream Manhole, Survey Ends - 02 1546A198.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish198.9 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK198.9 ft. VC - Vermin Cockroach

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
73TF
198.9AMH02 1546A
146.2TFC
0VC
5.1CM
0MWL
0AMH02 1547
148.9TFC
174.2TF
98.2TF
198.9CM
47.6TFC
198.9MGOLATERAL AT MH 9 OCLOCK
0MGOLATERAL AT MH 9 OCLOCK
0MWM
50.5TF
123.6TFC
95.7TF
70.5TFC
198.9VC

Properties (5)

additional_info
SC224965
custom_field_two
3
customer
LACSD
datetime
2016-01-13T00:57:45-08:00
sewer_category