Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2017, 07:45 PM
  • A 0318_A 0317_5232017_131943.mp4

Date
05/23/2017
W/O
0640653
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00325
PipeID
P08228
Time
12:45 PM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7413
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20170523MI_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
63 in.
Upstream MH
A 0318
Downstream MH
A 0317
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
12
Pipe schematic from manhole A 0318 to A 0317
MH: A 0318MH: A 0317downstream0 ft. MGO - General Observation - AIRLINE AT THE MH, 12 OCLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01:30 PM0 ft. MWL - Water Level, 100 %of cross sectional area2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. LD - Alignment Down, 45 %2.1 ft. MGO - General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON2.1 ft. MSA - Survey Abandoned - SIPHON INSPECTION OF DOWNLEG PIPE OF THE U/S SIPHON

Observation photos (4)

  • General Observation - AIRLINE AT THE MH, 12 OCLOCK

    0 ft. - General Observation - AIRLINE AT THE MH, 12 OCLOCK

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

    2.1 ft. - General Observation - VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON

Observations (8)

DistanceCodeObservation
2.1MGOVIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
0MGOAIRLINE AT THE MH, 12 OCLOCK
2SAP
2.1MSASIPHON INSPECTION OF DOWNLEG PIPE OF THE U/S SIPHON
2SRV
0AMH01:30 PM
0MWL
2LD

Properties (4)

additional_info
VIEW OF THE DOWNLEG PIPE OF THE U/S SIPHON
custom_field_two
2
customer
LACSD
datetime
2017-05-23T12:45:53-07:00