Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 23, 2017, 04:04 PM
  • A 0328_A 0327_5232017_095559.mp4

Date
05/23/2017
W/O
0640653
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00325
PipeID
P08238
Time
9:04 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7413
Sewer Name
A JOA-1A SAN JOSE CREEK WRP INTERCEPTOR
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
22
Purpose
Capital Improvement Program Assesment
Project
20170523MI_JOA_1A_SAN_JOSE_CREEK_WRP_INTERCEPTOR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
A 0327
Downstream MH
A 0328
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
9
Pipe schematic from manhole A 0327 to A 0328
MH: A 0327MH: A 0328upstream0 ft. MSA - Survey Abandoned - VIEW OF UPLEG PIPE OF D/S SIPHON0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES0 ft. MGO - General Observation - VIEW OF UPLEG PIPE OF THE D/S SIPHON0 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. LU - Alignment Up, 45 %2.1 ft. AMH - Downstream Manhole, Survey Begins - 10:00 AM2.1 ft. MGO - General Observation - AIRLINE AT MH, 12 OCLOCK2.1 ft. MWL - Water Level, 100 %of cross sectional area

Observation photos (4)

  • General Observation - AIRLINE AT MH, 12 OCLOCK

    0 ft. - General Observation - AIRLINE AT MH, 12 OCLOCK

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - VIEW OF UPLEG PIPE OF THE D/S SIPHON

    2.1 ft. - General Observation - VIEW OF UPLEG PIPE OF THE D/S SIPHON

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0AMH10:00 AM
2.1MSAVIEW OF UPLEG PIPE OF D/S SIPHON
2LU
2.1SAV
2.1MGOVIEW OF UPLEG PIPE OF THE D/S SIPHON
0MGOAIRLINE AT MH, 12 OCLOCK
2.1SSS
0MWL

Properties (4)

additional_info
VIEW OF THE UPLEG PIPE OF THE D/S SIPHON
custom_field_two
2
customer
LACSD
datetime
2017-05-23T09:04:24-07:00