Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2016, 06:25 AM
  • 19 0048_19 0047_20160317_000550.mp4

Date
03/16/2016
W/O
557873
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00724
PipeID
P15078
Time
11:25 PM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3226
Sewer Name
19 ELAINE AVENUE TRUNK
City
LAKEWOOD, CA
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
09
Purpose
Routine Assessment
Project
WO_557873_TV19004_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Upstream MH
19 0047
Downstream MH
19 0048
Dir. of Survey
Upstream
Length Surveyed
385.4 ft.
Total Length
385.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3121
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 19 0047 to 19 0048
MH: 19 0047MH: 19 0048upstream0 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 19 004813.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"16 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"61.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"65 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"113.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"118.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4" - W/ MINERAL DEPOSITS120.6 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO165.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"169.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"213.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"218 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"261.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"266.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"313.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"317.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"365.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4" - W/ MINERAL DEPOSITS369.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"381.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES, Start385.4 ft. AMH - Downstream Manhole, Survey Begins - 19 0047385.4 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK385.4 ft. MWL - Water Level, 35 %of cross sectional area385.4 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK385.4 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (1)

  • Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4" - W/ MINERAL DEPOSITS

    267.3 ft. - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4" - W/ MINERAL DEPOSITS

Observations (25)

DistanceCodeObservation
0AMH19 0047
0MGOLATERAL AT MH 9 OCLOCK
119.1TFC
372.1TFC
320.4TFC
71.9TFC
123.5TFC
68TFC
369.4TFC
264.8ID
219.7TFC
323.9TFC
267.3TFCW/ MINERAL DEPOSITS
167.4TFC
215.8TFC
0MWL
19.6TFCW/ MINERAL DEPOSITS
171.5TFC
0MGOLATERAL AT MH 3 OCLOCK
271.5TFC
385.4DAE
0MWM
385.4AMH19 0048
15.7TFC
4.3DAE

Properties (5)

additional_info
SC305317
custom_field_two
4
customer
LACSD
datetime
2016-03-16T23:25:49-07:00
sewer_category
GRAVITY