Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 7, 2016, 09:27 AM
  • 19 0073_19 0072_20160307_025513.mp4

Date
03/07/2016
W/O
557873
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z00724
PipeID
P15105
Time
1:27 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3217
Sewer Name
19 ELAINE AVENUE TRUNK
City
LAKEWOOD, CA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 19
Page No.
06
Purpose
Routine Assessment
Project
WO_557873_TV19004_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
19 0073
Downstream MH
19 0072
Dir. of Survey
Downstream
Length Surveyed
315.3 ft.
Total Length
315.3 ft.
Structural Index
2
Structural Quick
3221
Structural Rating
9
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
147
Pipe schematic from manhole 19 0073 to 19 0072
MH: 19 0073MH: 19 0072downstream0 ft. AMH - Upstream Manhole, Survey Begins - 19 00730 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start12.6 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES44.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 12 to 03 o'clock, , within 8 inches of joint: YES58.1 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"109.7 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"158.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"203.5 ft. CC - Crack Circumferential, from 03 to 09 o'clock, within 8 inches of joint: YES207.8 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"250.7 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"268.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES270.7 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES304.3 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES305.9 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4", 4"312.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish315 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK315.3 ft. AMH - Downstream Manhole, Survey Ends - 19 0072

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Circumferential, from 03 to 09 o'clock, within 8 inches of joint: YES

    203.5 ft. - Crack Circumferential, from 03 to 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    268.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    270.7 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    304.3 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
0AMH19 0073
315.3AMH19 0072
268.2CL
203.5CC
304.3CM
315MGOCONNECTION AT THE MH 9 O' CLOCK
58.1TBC
270.7CM
0MWM
305.9TBC
109.7TBC
7DAGS
250.7TBC
12.6DAZ
312.9DAGS
158.8TBC
44.4DAE
207.8TBC
0MWL

Properties (5)

additional_info
SC305307
custom_field_two
3
customer
LACSD
datetime
2016-03-07T01:27:35-08:00
sewer_category
GRAVITY