Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 4, 2016, 12:31 PM
  • 29 0738_29 0317_20160304_054133.mp4

Date
03/04/2016
W/O
557696
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01017
PipeID
P24350
Time
4:31 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3217
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_557696_TV29045_2016MAR
Material
NRCP
Shape
Circular
Height
8 in.
Upstream MH
29 0738
Downstream MH
29 0317
Dir. of Survey
Downstream
Length Surveyed
163.8 ft.
Total Length
163.8 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
91
Pipe schematic from manhole 29 0738 to 29 0317
MH: 29 0738MH: 29 0317downstream0 ft. AMH - Upstream Manhole, Survey Begins - 29 07380 ft. MWL - Water Level, 5 %of cross sectional area12 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start22.1 ft. VC - Vermin Cockroach37.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"37.8 ft. MGO - General Observation - PIPE IS CONCRETE PIPE63.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"79.7 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"86.7 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"114.6 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"140.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"161 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish162.6 ft. MGO - General Observation - DROP CONNECTIONAT MANHOLE163.8 ft. AMH - Downstream Manhole, Survey Ends - 29 0317

Observation photos (2)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    12 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • General Observation - DROP CONNECTIONAT MANHOLE

    162.6 ft. - General Observation - DROP CONNECTIONAT MANHOLE

Observations (14)

DistanceCodeObservation
163.8AMH29 0317
37.8TFA
79.7TFA
140.2TFA
86.7TFA
63.5TF
161SAV
162.6MGODROP CONNECTIONAT MANHOLE
0AMH29 0738
37.8MGOPIPE IS CONCRETE PIPE
22.1VC
12SAV
0MWL
114.6TF

Properties (5)

additional_info
SC305306
custom_field_two
3
customer
LACSD
datetime
2016-03-04T04:31:58-08:00
sewer_category