Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2016, 06:39 AM
  • 29 0334_29 0333_20160302_235619.mp4

Date
03/02/2016
W/O
557696
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01017
PipeID
P24353
Time
10:39 PM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3216
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_557696_TV29045_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0334
Downstream MH
29 0333
Dir. of Survey
Downstream
Length Surveyed
295 ft.
Total Length
295 ft.
Structural Index
2
Structural Quick
2111
Structural Rating
3
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
4
Pipe schematic from manhole 29 0334 to 29 0333
MH: 29 0334MH: 29 0333downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 29 033411.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: NO25.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 4"29.2 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"95.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"99.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"121.7 ft. CC - Crack Circumferential, from 07 to 11 o'clock, within 8 inches of joint: YES129.5 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"132.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4"179.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"182.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"223 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"226.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"283 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"295 ft. VC - Vermin Cockroach295 ft. AMH - Downstream Manhole, Survey Ends - 29 0333

Observation photos (1)

  • Crack Circumferential, from 07 to 11 o'clock, within 8 inches of joint: YES

    121.7 ft. - Crack Circumferential, from 07 to 11 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
283TF
121.7CC
29.2TFA
0MWL
0MWM
182.8TFA
132.8TF
223TF
11.6CL
295VC
99.2TF
95.8TF
129.5TF
179.8TF
226.4TFC
295AMH29 0333
0AMH29 0334
25.8TFA

Properties (5)

additional_info
SC305305
custom_field_two
4
customer
LACSD
datetime
2016-03-02T22:39:24-08:00
sewer_category
GRAVITY