Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2016, 12:13 PM
  • 29 0344_29 0343_20160303_053215.mp4

Date
03/03/2016
W/O
557696
Weather
Dry
Operator/Surveyor
J. HARTOOG
Sewer ID
Z01017
PipeID
P24365
Time
4:13 AM
Certificate
U507-03-3386
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K3216
Sewer Name
29 PACIFIC COAST HIGHWAY SEWER
City
SIGNAL HILL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 29
Page No.
03
Purpose
Routine Assessment
Project
WO_557696_TV29045_2016MAR
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
29 0343
Downstream MH
29 0344
Dir. of Survey
Upstream
Length Surveyed
372.7 ft.
Total Length
372.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 29 0343 to 29 0344
MH: 29 0343MH: 29 0344upstream0 ft. ACOM - Cleanout Mainline - 29 03442.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4"4.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"40.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"42.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"65.3 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"89.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"95.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"98.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 4"141.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"188.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"191.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"238.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"241.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"242.8 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES288.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"290.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"329 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"337.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"372.7 ft. MWL - Water Level, 5 %of cross sectional area372.7 ft. VC - Vermin Cockroach372.7 ft. MWM - Water Mark, 10 %of cross sectional area372.7 ft. MGO - General Observation - TROUGH BROKEN372.7 ft. AMH - Downstream Manhole, Survey Begins - 29 0343

Observation photos (1)

  • Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

    307.4 ft. - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

Observations (24)

DistanceCodeObservation
0MWL
0VC
181.1TFC
277.4TFC
368TF
35.5TF
330TFC
282.8TFC
81.8TFC
134.2TFC
129.9CM
43.7TFA
307.4TBA
274.2TB
332.6TFC
370.2TF
372.7ACOM29 0344
0MWM
0MGOTROUGH BROKEN
230.8TFC
183.8TFC
0AMH29 0343
84.5TFC
131.5TFC

Properties (5)

additional_info
SC305305
custom_field_two
4
customer
LACSD
datetime
2016-03-03T04:13:00-08:00
sewer_category
GRAVITY