Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2016, 12:00 PM
  • B 0853_B 0481_17032016_050045.mp4

Date
03/17/2016
W/O
557614
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00096
PipeID
P09007
Time
5:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3296
Sewer Name
B JOINT OUTFALL B - UNIT 6B
City
ROSEMEAD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_557614_TV15108_2016MAR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
B 0853
Downstream MH
B 0481
Dir. of Survey
Downstream
Length Surveyed
457 ft.
Total Length
457 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
273
O&M Index
2
O&M Quick
2Q00
O&M Rating
182
Overall Index
3
Overall Quick
Overall Rating
455
Pipe schematic from manhole B 0853 to B 0481
MH: B 0853MH: B 0481downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 08530 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start363.3 ft. MGO - General Observation - RUN LIST STATES MH AT 363'.456.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish456.1 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish456.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE456.1 ft. MGO - General Observation - CAPPED CONNECTION AT MH 3 O'CLOCK457 ft. AMH - Downstream Manhole, Survey Ends - B 0481

Observation photos (3)

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    456.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0MWM
456.1DAGS
0AMHB 0853
363.3MGORUN LIST STATES MH AT 363'.
456.1SAP
2SAP
456.1MGOCOCKROACHES IN MANHOLE
456.1MGOCAPPED CONNECTION AT MH 3 O'CLOCK
0MWL
2DAGS
457AMHB 0481
0MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC305420
custom_field_three
PROJECTING AGG THROUGHOUT
custom_field_two
3
customer
LACSD
datetime
2016-03-17T05:00:23-07:00
sewer_category
GRAVITY