Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 16, 2016, 09:13 AM
  • B 0859_B 0858_16032016_021349.mp4

Date
03/16/2016
W/O
557614
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00096
PipeID
P09013
Time
2:13 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3294
Sewer Name
B JOINT OUTFALL B - UNIT 6B
City
ROSEMEAD
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
21
Purpose
Routine Assessment
Project
WO_557614_TV15108_2016MAR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Upstream MH
B 0859
Downstream MH
B 0858
Dir. of Survey
Downstream
Length Surveyed
616.3 ft.
Total Length
616.3 ft.
Structural Index
3
Structural Quick
3X00
Structural Rating
369
O&M Index
2
O&M Quick
2X00
O&M Rating
246
Overall Index
3
Overall Quick
Overall Rating
615
Pipe schematic from manhole B 0859 to B 0858
MH: B 0859MH: B 0858downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 08590 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start614.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish614.9 ft. MGO - General Observation - RUN LIST STATES MH AT 728.'614.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish616.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE616.3 ft. AMH - Downstream Manhole, Survey Ends - B 0858

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    616.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
0MWL
0AMHB 0859
614.9DAGS
0MWM
614.9MGORUN LIST STATES MH AT 728.'
0MGOCOCKROACHES IN MANHOLE
2DAGS
616.3MGOCOCKROACHES IN MANHOLE
614.9SAP
616.3AMHB 0858
2SAP

Properties (6)

additional_info
SC305418
custom_field_three
PROJECTING AGG THROUGHOUT
custom_field_two
3
customer
LACSD
datetime
2016-03-16T02:13:16-07:00
sewer_category
GRAVITY