Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2016, 06:58 AM
  • 08 0550_08 0549_16032016_235817.mp4

Date
03/16/2016
W/O
557595
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00015
PipeID
P00136
Time
11:58 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3295
Sewer Name
08 MAIN STREET RELIEF TRUNK
City
CARSON
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
WO_557595_TV08024_2016MAR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
39 in.
Upstream MH
08 0550
Downstream MH
08 0549
Dir. of Survey
Downstream
Length Surveyed
672.1 ft.
Total Length
672.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Z00
O&M Rating
268
Overall Index
2
Overall Quick
Overall Rating
268
Pipe schematic from manhole 08 0550 to 08 0549
MH: 08 0550MH: 08 0549downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 08 05500 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start4.4 ft. MGO - General Observation - MAG COATING 40%669.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish672.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0549672.1 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
672.1AMH08 0549
0MWL
672.1MGOACTIVE CONNECTION AT MH 9 O'CLOCK
2DAGS
0AMH08 0550
0MWM
669.7DAGS
4.4MGOMAG COATING 40%

Properties (6)

additional_info
SC305419
custom_field_two
4
customer
LACSD
datetime
2016-03-16T23:58:02-07:00
sewer_category
GRAVITY
year_laid
19720923