Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 8, 2016, 06:03 AM
  • 08 0113_08 0112_07032016_220346.mp4

Date
03/07/2016
W/O
557595
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00015
PipeID
P00163
Time
10:03 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3279
Sewer Name
08 MAIN STREET RELIEF TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
04
Purpose
Routine Assessment
Project
WO_557595_TV08024_2016MAR
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
08 0113
Downstream MH
08 0112
Dir. of Survey
Downstream
Length Surveyed
530.1 ft.
Total Length
530.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2T00
O&M Rating
210
Overall Index
2
Overall Quick
Overall Rating
210
Pipe schematic from manhole 08 0113 to 08 0112
MH: 08 0113MH: 08 0112downstream0 ft. AMH - Upstream Manhole, Survey Begins - 08 01130 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. MGO - General Observation - MAG COATING 75%2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start50.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"110.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.5 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"280 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"344.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"401.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"465.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"522.3 ft. TBA - Tap Break-In Active, at 01 o'clock, -, within 8 inches of joint: NO, 6"528.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish530.1 ft. AMH - Downstream Manhole, Survey Ends - 08 0112

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
344.5TFC
522.3TBA
465.6TFC
401.2TBA
0AMH08 0113
528.1DAGS
0MWM
110.6TFC
2MGOMAG COATING 75%
2DAGS
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0MWL
280TFC
166.7TFC
530.1AMH08 0112
50.9TBA
231.5TBA

Properties (5)

additional_info
SC305403
custom_field_two
4
customer
LACSD
datetime
2016-03-07T22:03:31-08:00
sewer_category
GRAVITY