Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2016, 06:11 AM
  • 02 0936_02 0935_20160106_225441_.mp4

Date
01/06/2016
W/O
546949
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00252
PipeID
P03505
Time
10:11 PM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2950
Sewer Name
02 DOWNEY-BELLFLOWER DIVERSION TRUNK
City
DOWNEY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
WO_546949_TV02053_JAN2016
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
02 0936
Downstream MH
02 0935
Dir. of Survey
Downstream
Length Surveyed
364.1 ft.
Total Length
364.1 ft.
Structural Index
2
Structural Quick
2B11
Structural Rating
31
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
31
Pipe schematic from manhole 02 0936 to 02 0935
MH: 02 0936MH: 02 0935downstream0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. MWL - Water Level, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 093618.3 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES49.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES59.5 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES64.7 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start124.8 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Finish136.6 ft. CC - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES364.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0935

Observation photos (5)

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    18.3 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    49.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    59.5 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

    64.7 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES, Start

  • Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

    136.6 ft. - Crack Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
136.6CC
124.8CL
0MWM
59.5CL
64.7CL
0MWL
49.5CL
0AMH02 0936
18.3CL
364.1AMH02 0935

Properties (5)

additional_info
SC224961
custom_field_two
3
customer
LACSD
datetime
2016-01-06T22:11:24-08:00
sewer_category