Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 16, 2015, 09:51 AM
  • B 0718A_B 0718_20151216_021013.mp4

Date
12/16/2015
W/O
542022
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00110
PipeID
P09393
Time
1:51 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K2933
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_542022_TV22067_DEC2015
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
B 0718
Downstream MH
B 0718A
Dir. of Survey
Upstream
Length Surveyed
258.2 ft.
Total Length
258.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
1
Overall Quick
Overall Rating
1
Pipe schematic from manhole B 0718 to B 0718A
MH: B 0718MH: B 0718Aupstream0 ft. VC - Vermin Cockroach0 ft. MGO - General Observation - CONNECTION AT THE MH 9 O' CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - B 0718A1.8 ft. MGO - General Observation - Magnesium hydroxide coating 70% finish5.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"8.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"11.2 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"52.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"56 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"56.4 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"97.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"100.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"154.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"157.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"202.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"205.6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 4"244.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 4"247.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"256.2 ft. MGO - General Observation - Magnesium hydroxide coating 70% start258.2 ft. MWM - Water Mark, 30 %of cross sectional area258.2 ft. MWL - Water Level, 5 %of cross sectional area258.2 ft. AMH - Downstream Manhole, Survey Begins - B 0718

Observations (22)

DistanceCodeObservation
55.8TFC
258.2VC
157.7TFC
202.2TF
52.6TFA
249.6TFC
205.5TFC
0MWM
256.4MGOMagnesium hydroxide coating 70% finish
13.7TFA
100.7TFC
10.3TFC
201.8TBA
252.8TFC
258.2MGOCONNECTION AT THE MH 9 O' CLOCK
2MGOMagnesium hydroxide coating 70% start
160.6TFC
247TBA
258.2AMHB 0718A
103.9TFA
0MWL
0AMHB 0718

Properties (5)

additional_info
SC207039
custom_field_two
4
customer
LACSD
datetime
2015-12-16T01:51:30-08:00
sewer_category