Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 1, 2017, 08:28 AM
  • 01 0443_01 0442_512017_024639.mp4

Date
05/01/2017
W/O
0624632
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00208
PipeID
P00925
Time
1:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0511
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
201700501MDM_HOLMES_WILLOWBROOK_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
01 0443
Downstream MH
01 0442
Dir. of Survey
Downstream
Length Surveyed
362.2 ft.
Total Length
362.2 ft.
Structural Index
3
Structural Quick
3623
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 01 0443 to 01 0442
MH: 01 0443MH: 01 0442downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 2:40AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. MGO - General Observation - MAG COAT 30% START 8:00 TO 4:002 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG10 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG10 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN38.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open47.6 ft. MGO - General Observation - MAG COAT 10% START71.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED87.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open92.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open97.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE107.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open113.8 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active141.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped143.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG154.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open156.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open190.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped199.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active203.9 ft. FC - Fracture Circumferential, from 07 to 09 o'clock, within 8 inches of joint: YES - SLIGHT204.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SLIGHT205.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open261.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open282.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open289.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE293.9 ft. MWM - Water Mark, 30 %of cross sectional area310.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open333.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6" - Open356.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open362 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED362 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES362 ft. MGO - General Observation - MAG COAT 10% FINISH362 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG362.2 ft. AMH - Downstream Manhole, Survey Ends - 3:20AM

Observation photos (8)

  • General Observation - MAG COAT 30% START 8:00 TO 4:00

    2 ft. - General Observation - MAG COAT 30% START 8:00 TO 4:00

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    10 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • General Observation - MAG COAT 10% START

    47.6 ft. - General Observation - MAG COAT 10% START

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED

    71.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - PEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

    97.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - PEELING CONCRETE

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

    143.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE AGG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE

    289.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES - SEVERE

Observations (36)

DistanceCodeObservation
204.6FLSLIGHT
2MGOMAG COAT 30% START 8:00 TO 4:00
113.8TBActive
156.6TFOpen
154.3TFOpen
92.5TFOpen
38.6TFOpen
310.2TFOpen
0MWM
261.7TFOpen
199.9TFActive
107.6TFOpen
47.6MGOMAG COAT 10% START
0AMH2:40AM
2SAVSEVERE AGG
362.2AMH3:20AM
293.9MWM
289.6SAVSEVERE
362SSSPEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED
203.9FCSLIGHT
97.9SSSPEELING CONCRETE
0MWL
356.9TFOpen
362SAV
362MGOMAG COAT 10% FINISH
10SAVSEVERE AGG
205.3TFOpen
190.2TFCCapped
362SAVSEVERE AGG
141.3TFCCapped
10TFOPEN
333.5TFOpen
143.5SAVSEVERE AGG
282.4TFOpen
71.5SSSPEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED
87.5TFOpen

Properties (4)

custom_field_three
PEELING CONCRETE POSSIBLE SEVERE AGG ATTCHED
custom_field_two
2
customer
LACSD
datetime
2017-05-01T01:28:19-07:00