Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 15, 2017, 11:16 AM
  • 15 1106_15 1105_5152017_041901.mp4

Date
05/15/2017
W/O
0630261
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00614
PipeID
P12866
Time
4:16 AM
Certificate
1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0526
Sewer Name
15 MERCED TRUNK, SECTION 1
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Capital Improvement Program Assesment
Project
20170515MDM_MERCED_TRUNK_SECTION_1
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
15 1106
Downstream MH
15 1105
Dir. of Survey
Downstream
Length Surveyed
300.2 ft.
Total Length
300.2 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 15 1106 to 15 1105
MH: 15 1106MH: 15 1105downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:20AM2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE39.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open70.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open128.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open139.8 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES - SLIGHT139.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SLIGHT185.3 ft. MGO - General Observation - 8" VCP185.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish239 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open251.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open300.2 ft. AMH - Downstream Manhole, Survey Ends - 5:00AM

Observation photos (1)

  • Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE

    3 ft. - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - HAIRLINE

Observations (15)

DistanceCodeObservation
0MWL
185.3MGO8" VCP
139.8FLSLIGHT
251.4TFOpen
70.6TFOpen
139.9FCSLIGHT
300.2AMH5:00AM
128.7TFOpen
239TFOpen
185.3DAGS
2DAGS
3FCHAIRLINE
0MWM
39.9TFOpen
0AMH4:20AM

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-05-15T04:16:14-07:00