- Date
- 05/08/2017
- W/O
- 0618889
- Weather
- Dry
- Operator/Surveyor
- FRANKLIN
- Sewer ID
- Z00315
- PipeID
- P07762
- Time
- 12:31 PM
- Certificate
- U-415-06024039
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7400
- Sewer Name
- A JOA-1A DISTRICT 5 INTERCEPTOR
- City
- TORRANCE
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 20
- Purpose
- Routine Assessment
- Project
- 20170508DF_JOA_1A_DISTRICT_5_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 54 in.
- Upstream MH
- A 0526
- Downstream MH
- A 0525
- Dir. of Survey
- Downstream
- Length Surveyed
- 370.6 ft.
- Total Length
- 370.6 ft.
- Structural Index
- 3
- Structural Quick
- 3221
- Structural Rating
- 8
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 8
Pipe schematic from manhole A 0526 to A 0525 Observation photos (8)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

62.2 ft. - General Observation - DEBRIS/RAGS

100.9 ft. - General Photograph - AGGREGATE

131.9 ft. - General Photograph - DEBRIS/RAGS

194.2 ft. - Surface Aggregate Visible, from 02 to 04 o'clock, within 8 inches of joint: YES

274.4 ft. - General Photograph - SPALLING/AGGREGATE

309.5 ft. - General Photograph - RAGS