Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 5, 2017, 05:25 PM
  • 05 1113_05 1092_552017_112935.mp4

Date
05/05/2017
W/O
0630075
Weather
Dry
Operator/Surveyor
IGNACIO
Sewer ID
Z00489
PipeID
P06348
Time
10:25 AM
Certificate
PENDING
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7398
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 2
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
20170505MI_MONETA_EXTENSION_TRUNK_SECTION_2
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Upstream MH
05 1113
Downstream MH
05 1092
Dir. of Survey
Downstream
Length Surveyed
365.8 ft.
Total Length
365.8 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
9
Pipe schematic from manhole 05 1113 to 05 1092
MH: 05 1113MH: 05 1092downstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:30 AM0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area3.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start127.2 ft. SSS - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES175.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"323 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES364.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish364.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish365.6 ft. MGO - General Observation - CONNECTION AT MH, 3 OCLOCK, ACTIVE365.7 ft. MGO - General Observation - CONNECTION AT MH, 9 OCLOCK, OPEN365.8 ft. AMH - Downstream Manhole, Survey Ends - 11:51 AM

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES

    127.2 ft. - Surface Spalling, from 11 to 01 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    175.3 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    323 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Observation - CONNECTION AT MH, 3 OCLOCK, ACTIVE

    365.6 ft. - General Observation - CONNECTION AT MH, 3 OCLOCK, ACTIVE

  • General Observation - CONNECTION AT MH, 9 OCLOCK, OPEN

    365.7 ft. - General Observation - CONNECTION AT MH, 9 OCLOCK, OPEN

  • Downstream Manhole, Survey Ends - 11:51 AM

    365.8 ft. - Downstream Manhole, Survey Ends - 11:51 AM

Observations (13)

DistanceCodeObservation
0AMH11:30 AM
127.2SSS
365.6MGOCONNECTION AT MH, 3 OCLOCK, ACTIVE
364.1SSS
0MWL
364.1DAGS
3.9SSS
365.8AMH11:51 AM
365.7MGOCONNECTION AT MH, 9 OCLOCK, OPEN
175.3TBA
6.3DAGS
323CM
0MWM

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2017-05-05T10:25:32-07:00