- Date
- 05/05/2017
- W/O
- 0624515
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00102
- PipeID
- P09140
- Time
- 2:28 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- HO516
- Sewer Name
- B JOINT OUTFALL B - UNIT 7 RELIEF
- City
- MONTEREY PARK
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 26
- Purpose
- Routine Assessment
- Project
- 20170505MDM_JOINT_OUTFALL_B_UNIT_7_RELIEF
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 15 in.
- Upstream MH
- B 0847
- Downstream MH
- B 0846
- Dir. of Survey
- Downstream
- Length Surveyed
- 240.4 ft.
- Total Length
- 240.4 ft.
- Structural Index
- 2
- Structural Quick
- 2300
- Structural Rating
- 6
- O&M Index
- 4
- O&M Quick
- 4231
- O&M Rating
- 11
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 17
Pipe schematic from manhole B 0847 to B 0846 Observation photos (3)

1.5 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO - IN MH UNDER FLOW

8 ft. - General Observation - 15" VCP

167.5 ft. - Repair Patch, from 09 to 11 o'clock, within 8 inches of joint: YES - CONCTETE PATCH