Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0May 3, 2017, 09:40 AM
  • B 0629_B 0628_532017_024820.mp4

Date
05/03/2017
W/O
0624373
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00107
PipeID
P09294
Time
2:40 AM
Certificate
U-1-14-06O22543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H0514
Sewer Name
B JOINT OUTFALL B - UNIT 8D
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
20170503MDM_JOINT_OUTFALL_B_UNIT_8D
Material
Reinforced Concrete Pipe
Shape
Circular
Height
27 in.
Upstream MH
B 0629
Downstream MH
B 0628
Dir. of Survey
Downstream
Length Surveyed
251.8 ft.
Total Length
251.8 ft.
Structural Index
2
Structural Quick
2400
Structural Rating
8
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole B 0629 to B 0628
MH: B 0629MH: B 0628downstream0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. STUB0 ft. AMH - Upstream Manhole, Survey Begins - 2:40AM2 ft. MGO - General Observation - MAG COAT 80% START 9:00 TO 3:002 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN ,FLAKING CONCRETE30.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN ,FLAKING CONCRETE68.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SLIGHT FLAKING195.6 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO251.3 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. OPEN251.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SWOLLEN,FLAKING CONCRETE251.8 ft. AMH - Downstream Manhole, Survey Ends - 3:05AM

Observation photos (5)

  • General Observation - MAG COAT 80% START 9:00 TO 3:00

    2 ft. - General Observation - MAG COAT 80% START 9:00 TO 3:00

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN ,FLAKING CONCRETE

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SWOLLEN ,FLAKING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN ,FLAKING CONCRETE

    30.9 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SWOLLEN ,FLAKING CONCRETE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SLIGHT FLAKING

    68.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - SLIGHT FLAKING

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

    195.6 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO

Observations (12)

DistanceCodeObservation
0MWM
2MGOMAG COAT 80% START 9:00 TO 3:00
251.3MGOConn. @ Mh, 9 O' Clock. OPEN
2SSSSWOLLEN ,FLAKING CONCRETE
195.6SSS
0MWL
30.9SSSSWOLLEN ,FLAKING CONCRETE
0MGOConn. @ Mh, 3 O' Clock. STUB
251.8AMH3:05AM
0AMH2:40AM
251.3SSSSWOLLEN,FLAKING CONCRETE
68.2SSSSLIGHT FLAKING

Properties (4)

custom_field_three
SPALLING CONCRETE
custom_field_two
4
customer
LACSD
datetime
2017-05-03T02:40:00-07:00